blog.iamechatronics.com
I.A.M. Journey : View life through an industrial technician's eyes: Calibration of Pyrometers using Black Body
http://blog.iamechatronics.com/2010/11/calibration-of-pyrometers-using-black.html
Iam Journey : View life through an industrial technician's eyes. Tuesday, November 9, 2010. Calibration of Pyrometers using Black Body. According to wikipedia, a Pyrometer is any non-contacting device that intercepts and measures thermal radiation. This measure is used to determine temperature, often of the object's surface. I have here some pictures while in the process of calibrating pyrometers using a black body. A brand new digital pyrometer from Ircon (Modline 3 Series). The plastic bag encasing...
instrumentationtubing.blogspot.com
Instrumentation Tubing and Their Connections: 16.0 References and Suggested Reading
http://instrumentationtubing.blogspot.com/2012/12/160-references-and-suggested-reading.html
Instrumentation Tubing and Their Connections. 160 References and Suggested Reading. 1 An installer’s pocket guide for Swagelok tube fittings: Swagelok instruction manual. 2 ANSI/ASME B31.1-1980: Power piping. 3 ISO-2186-1973 (2001): Fluid flow in closed conduits- connections for pressure signal transmissions between primary and secondary elements. 4 SA 655: Specification for special requirements for pipe and tubing for nuclear and other special applications. 9 ASME PTC code 19.5: Flow measurement. 18 BS-...
instrumentationtubing.blogspot.com
Instrumentation Tubing and Their Connections: 11.0 Impulse Tube/Sensing Line Support
http://instrumentationtubing.blogspot.com/2012/12/110-impulse-tubesensing-line-support.html
Instrumentation Tubing and Their Connections. 110 Impulse Tube/Sensing Line Support. Following principals should be followed while designing the instrument sensing line supports. Hanger, support and clamps design should include provision for seismic, pipe whip and thermal expansion of process taps and instrument sensing lines to which the hangers, supports or clamps may be subjected during normal operation, seismic or other credible events. Once you’ve taken the time to make good bends and installe...
blog.iamechatronics.com
I.A.M. Journey : View life through an industrial technician's eyes: November 2010
http://blog.iamechatronics.com/2010_11_01_archive.html
Iam Journey : View life through an industrial technician's eyes. Tuesday, November 9, 2010. Calibration of Pyrometers using Black Body. According to wikipedia, a Pyrometer is any non-contacting device that intercepts and measures thermal radiation. This measure is used to determine temperature, often of the objects surface. Notes on Pyrometer Calibration Procedure. Monday, November 1, 2010. Subscribe to: Posts (Atom). Calibration of Pyrometers using Black Body. Notes on Pyrometer Calibration Procedure.
instrumentationtubing.blogspot.com
Instrumentation Tubing and Their Connections: 1.0 Introduction to Instrumentation Tubing
http://instrumentationtubing.blogspot.com/2012/12/introduction-to-instrumentation-tubing.html
Instrumentation Tubing and Their Connections. 10 Introduction to Instrumentation Tubing. Impulse sensing lines are the lines containing process fluid which run between the sensing instruments and process tapping points, and are usually made of tubing/piping, valves and tube fittings. 11 Difference between a pipe and a tube. The fundamental difference between pipe and tube is the dimensional standard to which each is manufactured. 12 Major Advantages of Tubing over Piping Systems. 8208; Tubing is less rig...
instrumentationtubing.blogspot.com
Instrumentation Tubing and Their Connections: 15.0 Welding Methods
http://instrumentationtubing.blogspot.com/2012/12/150-welding-methods_4502.html
Instrumentation Tubing and Their Connections. 151 300 Series Stainless Steels. As this process runs “hotter” than the stick process, the use of a backing gas is mandatory. It should be noted that in welding the relatively small fitting sizes, filler deposition rate economies are not a factor and therefore the MIG method is not commonly applied. 152 C1018 Steel Fittings. What Metals can be welded using the TIG process? 154 ORBITAL TUBE WELDING. Orbital welding was first used in the 1960's when the aerospa...
gasturbinetutorial.blogspot.com
Gas Turbine Tutorials: July 2013
http://gasturbinetutorial.blogspot.com/2013_07_01_archive.html
Introduction to Gas Turbines. General, Functional Description. A package power plant, as furnished for most installations, is comprised of the single-shaft, simple cycle, heavy duty gas turbine unit driving a generator. Fuel and air are used by the gas turbine unit to produce the shaft horsepower necessary to drive certain accessories and ultimately the driven load generator. About Gas Turbine Units. At the instant one or both of the two spark plugs equipped combustion chambers is ignited, the remaining ...
gasturbinetutorial.blogspot.com
Gas Turbine Tutorials: Gas Turbine Heat Exchanger and Filters
http://gasturbinetutorial.blogspot.com/2013/06/gas-turbine-heat-exchanger-and-filters.html
Gas Turbine Heat Exchanger and Filters. Lube Fluid Heat Exchanger. Main lube filtering system - Filtration of all lube oil is accomplished by a 5 micron, pleated paper filter installed in the lube system just after the lube oil heat exchanger. One (duplex) filter is used with a transfer valve installed between the filters to direct oil flow through either filter and into the lube oil header. 2 -Operate the transfer valve with a wrench to bring the standby filter into service. 3 -Close the filler valve.
instrumentationtubing.blogspot.com
Instrumentation Tubing and Their Connections: 10.0 Installation of Instrumentation Tubing
http://instrumentationtubing.blogspot.com/2012/12/100-installation-of-instrumentation_7603.html
Instrumentation Tubing and Their Connections. 100 Installation of Instrumentation Tubing. 101 Best practices for impulse tubing installation. Separation between redundant instrument sensing lines should be provided by free air space or barriers or both such that no single failure can cause the failure of more than one redundant sensing line. The minimum separation between redundant sensing lines should be at least 450 mm. As an alternate a suitable steel or concrete barrier can be used. The distance of t...